The Cyrix-Li-Charge will connect a battery charger with 3 seconds delay:
if the charge disconnect output of the VE.Bus BMS is high, and
if it senses 13,7 V (resp. 27,4 V or 54,8 V) or more on its battery charger connection terminal, and
if it senses 2 V or more on its battery terminal (the Cyrix will remain open if not connect to the battery).
The Cyrix-Li-Charge will disengage immediately whenever its control input becomes free floating, signalling cell over voltage or cell over temperature.
In general a cell over voltage alarm will reset shortly after charging has been stopped. The Cyrix will then reconnect the charger after a delay 3 seconds. After 2 attempts to reengage with 3 seconds delay, the delay increases to 10 minutes. Whenever battery voltage is less than 13,5 V (resp. 27 V or 54 V), the Cyrix will disengage with a delay of 1 hour. Note 1: In case of zero discharge current, or a small discharge current, the Cyrix will not disengage shortly after the charger has been switched off and/or disconnected, because battery voltage will remain higher than 13,5 V. Note 2: If, after the Cyrix has disengaged, the output of the battery charger immediately increases to 13,7 V or more, the Cyrix will reengage, with 3 seconds delay.
Technical Specifications
Brand |
Victron Energy
|
Manufacturer Part Number |
CYR020230430
|
Voltage |
24/48
|
Continuous current & Breaking capacity at 12V or 24V |
230A
|
Current Consumption When Open |
4 mA
|
Control Cable Included (Length 1 m) |
Yes
|
LED Status Indication |
Yes
|
Protection Category |
IP54
|
Dimensions |
H65 x W100 x D50mm
|
Weight (kg) |
0.27
|
Warranty |
5 Years
|
Country of Manufacture |
Malaysia